S2000-KDL Bolid Two-wire communication line controller. Two-wire communication line controller Bolid S2000-KDL S2000 kdl current consumption

S2000-KDL Two-wire communication line controller
up to 127 detectors (zones, loops) powered from this line, controlled from the S2000 remote control or a computer via the RS-485 interface

Features S2000-KDL

The S2000-KDL two-wire communication line controller, which is part of the Orion integrated security system as an integral part of a combined expandable addressable analog device, is designed to protect objects from penetration and fires by monitoring the state of addressable inputs (inputs), which can be represented by addressable security, fire and security fire detectors and / or controlled circuits (CC) of addressable expanders (AR); control, through the outputs of addressable signal-starting units (SP) and control, through addressable inputs (addressable detectors and / or KC addressable expanders), fire protection systems (alarm, smoke removal, fire arrest and other actuating devices).
The controller provides connection of up to 127 addressable devices (AD) to a two-wire communication line (DPLS).
The controller operates as an addressable device within the network of devices of the Orion integrated security system under the control of the network controller. The network controller can be a control panel "S2000" or "S2000M", as well as a computer with installed software AWP "Orion" or "Orion Pro".
The controller is powered by one or two (main + backup) DC sources of 12 V or 24 V.
The controller does not issue false notifications when exposed to external electromagnetic interference of the third degree of severity according to GOST R 50009.
Radio interference generated by the controller does not exceed the values ​​specified in GOST R 50009.
The S2000-KDL controller is intended for installation inside closed, unheated premises and is designed for round-the-clock operation. The design of the controller does not provide for its use in conditions of exposure to aggressive environments, dust, as well as in explosion-hazardous rooms.

Specifications S2000-KDL

Number of connected AUs 127
Two-wire line length 600 meters with a cross section of 0.75 mm²
700 meters with a cross section of 0.9 mm²
Supply voltage 10.2 V to 28.4 V DC
Consumption current (excluding AC consumption), not more than: at supply voltage 12 V 80 mA
at 24 V supply voltage 40 mA
Current consumption in standby mode (127 AUs are connected with a consumption current of 0.5 mA each), not more than: at supply voltage 12 V 160 mA
at 24 V supply voltage 80 mA
External reader of electronic identifiers (EI) 1 entry
Connected reader interface Dallas Touch Memory(1-Wire, µ-LAN), Wiegand and ABA-Track II
Reader LED control Control of two reader LEDs (red and green) in accordance with the logic levels "+5V CMOS", with current limiting with direct connection of LEDs at the level of 10 mA
Reader buzzer control Eat. Control signal "+5V CMOS"
Memory capacity of Touch Memory(iButton) keys, cards or codes 512
Non-volatile event buffer 255
Light indication on the front panel 3 LED indicators (operation, RS-485 and DPLS)
Built-in buzzer Not less than 50 dBA at a distance of 1 m
Tamper sensor microcontact
Communication port (for work in ISO "Orion") RS-485, Orion protocol
Instrument power supply From an external DC source (There is an additional input for connecting a backup power source)
Ready for operation after power on no more than 15 s
Working temperature range from minus 30 to +55°C
Relative Humidity up to 98% at +25°C
Case protection degree IP30
dimensions 156×107×39mm
Device weight no more than 0.3 kg
Average service life 10 years
Controller Programming UProg.exe program
PC connection via the RS-485 interface using an interface converter
Mounting type wall mounted or DIN rail

Package Included:

1) S2000-KDL controller;
2) a passport with a mark of acceptance and indicating the serial number of the controller;
3) installation instructions;
4) a set of spare parts and accessories:
- screw 1-3 × 25.016 GOST 1144-80 - 3 pcs.;
- dowel 6 × 30 (for screws 3 × 25) - 3 pcs.;
- self-tapping screw 2.2 × 6.5 oz. DIN 7982 - 1 pc.

Installation and configuration of the controller are carried out in accordance with the Operation Manual, as well as RD 78.145-93.
The controller has no dangerous voltage circuits.
Mounting, installation and maintenance should be carried out with the power supply of the controller switched off.

Purpose:
Controller of the addressable two-wire subsystem for the transmission of notifications "SPI-2000A" ("S2000-KDL-2I" with galvanic isolation). It is possible to work only as part of the ISO "Orion" system

Main characteristics:
Connecting up to 127 addressable devices (AU).
Ring two-wire communication line with short circuit and open circuit monitoring
The presence of galvanically isolated groups of wired connections - power supply, RS485 interface
Possibility of using short-circuit insulators "BRIZ" and "BRIZ isp.01"
Power supply of connected addressable devices via a two-wire communication line
Work with analog addressable smoke detectors "DIP-34A":
assignment of the warning threshold "Attention" and the threshold "Fire"
setting the time zones "Day" and "Night" with the assignment of thresholds "Attention" and "Fire" separately for each time zone
dust level assignment
transmission of notifications "Service Required", "Attention", "Fire", "Fault"
Work with addressable fire detectors "S2000-IP" and "IPR 513-ZA"
Work with two-address flow meters "S2000-ACP2", designed to count impulses coming from mechanical or electric meters (water, electricity, gas)
Connection of addressable security detectors "S2000-IK", "S2000-SHIK", "S2000-PIK", "S2000-ST", "S2000-SMK", "S2000-SMK Estet", "S2000-B", "S2000- microwave”, “S2000-STIK”, “S2000-CT”
Work with the address humidity and temperature meter "S2000-BT"
Connection to a two-wire communication line of non-address security and fire detectors with a "dry contact" output through addressable expanders "S2000-AP1", "S2000-AP2" and "S2000-AP8"
Control of executive devices through the addressable relay block "S2000-SP2"
Connecting Touch Memory (iButton) key readers, Proximity cards, and PIN code keypads
Support for reader interfaces - Touch Memory(iButton), Wiegand and ABA-TrackII
Local and centralized management of partitions (zones). Sections (zones) status indication is carried out on the reader's remote LED (single or two-color)
Transfer of service and alarm messages to the S2000, S2000M, Orion workstations and Orion Pro workstations
Transfer on request to the RS-485 interface of the resistance values ​​of the loops of addressable expanders, the values ​​of smoke and ambient temperature from "DIP-34A" and "S2000-IP", respectively
Use in conjunction with "S2000-VT" and "S2000-IP" to measure humidity and temperature with changing thresholds for turning on and off actuators
The execution and design of the controller complies with the European standard EN54
Block opening control
Light indication of the status of the device, RS-485 interface
Two power inputs: for connecting the main and backup power sources, voltage from 12 V to 24 V. A failure of the power supply line of one of the sources (short circuit or open circuit) does not affect the operation of the other

Buy the S2000-KDL car from Layta at an attractive price. Car S2000-KDL: description, specifications, customer reviews, photos and related products..

Building analog addressable security systems based on the S2000-KDL controller

The S2000-KDL two-wire communication line controller is one of the main elements of the analog addressable subsystem of the Orion Bolide. The device constantly monitors all devices connected to it with further transmission of signals via RS-485 to the S2000/S2000M console.

Up to 127 different addressable devices are connected to the S2000-KDL addressable loop, ranging from security and fire detectors to flow meters and relay modules. However, it should be noted that some devices occupy not 1, but several addresses in the system at once. Therefore, it would be more correct to count not the devices, but the addresses occupied by them. This will avoid overloading the loop and incorrect operation of the controller itself.

The ring topology of the device loop significantly increases the reliability of the system, because in the event of a short circuit or a break in the loop, the address line will simply be divided into 2 parts, while remaining fully operational. In this case, all system devices (except for damaged ones) will continue to work as usual. In addition, it is possible to create branches from the main line with the connection of conventional devices to it. For this, special address expanders for 1 or several devices are used.

To protect the address loop and devices from short circuit, branching-insulating blocks Breeze and Breeze version 01 are installed in the loop. The devices allow you to cut off short-circuited sections of the address loop, thereby blocking further damage to the system. Also, with the use of BREEZE, it is possible to create a loop with a "tree" topology. The device is placed at the branch point and, in the event of a short circuit, cuts off the entire branch completely.

The S2000-KDL controller is also equipped with a circuit for connecting readers operating via the Touch Memory or Wiegand interface, which can be used to control the controller inputs.

On the basis of the S2000-KDL controller, it is also possible to organize security systems for explosive premises. In this case, the S2000-BRSHS-Ex alarm loop extension unit is used, which provides protection at the level of an intrinsically safe circuit. The device is installed outside the protected area and monitors 2 intrinsically safe loops with information relaying to S2000-KDL.

S2000-KDL operates exclusively under the control of S2000 and S2000M network controllers. The device constantly exchanges data with them, transmits alarm messages to the consoles and executes commands received from the consoles via RS-485. Notifications are transmitted with reference to date and time (internal clock with synchronization function).

Since the controller communicates with control panels and workstations via the RS-485 interface, there is no need to install all the equipment in one room. This feature allows you to build distributed systems in which S2000-KDL devices are placed as close as possible to controlled areas. In this case, control is carried out from a remote control or fire station of the building. Such systems can significantly reduce the cost of cable products, simplify and speed up the installation and maintenance of cable lines and equipment.